UPS Battery Backup Runtime Estimator
Lead-acid UPS batteries lose effective capacity sharply under heavy loads โ a phenomenon called the Peukert effect. Select a popular UPS model or enter your own specs and equipment load to get a realistic runtime estimate and discharge curve.
- Total load
- โ
- Effective pack
- โ
- Peukert derating
- โ
Runtime vs. Load Curve (10%โ100% UPS Capacity)
| Load Tier | Watts | Linear Est. | Peukert Runtime | Shutdown Window |
|---|
Why simple Wh รท Watts overestimates UPS runtime
Most consumer and rackmount UPS units use sealed lead-acid (SLA / AGM) batteries whose Ah capacity is rated at a gentle 20-hour discharge rate (C/20). During a blackout, a desktop PC or server pulls that battery down in 5 to 20 minutes โ a discharge rate 60ร to 240ร faster than rated.
At high discharge currents, internal chemical resistance causes battery voltage to sag early and hit the UPS low-voltage cutoff long before all nominal Watt-hours are extracted. This nonlinear drop is modeled by Peukert's Law:
t = 20 ร (E_usable รท (20 ร P_dc))^k
For SLA/AGM batteries, the Peukert exponent k is typically around 1.18โ1.25 (we use 1.20), which can cut usable runtime by 35โ55% at heavy loads. Modern LiFePO4 portable power stations and lithium UPS units have a much flatter discharge curve (k โ 1.03), delivering close to their full rated Wh even near maximum output.
UPS sizing and safe shutdown best practices
- Target under 70โ80% rated wattage: Running a UPS right at its 100% ceiling leaves no headroom for GPU transient spikes or compressor/drive spin-up, and produces only 2โ4 minutes of backup.
- Account for battery aging: SLA UPS batteries typically last 3โ5 years. By year 3, a battery may deliver only 65โ70% of its day-one runtime.
- Automate graceful shutdowns: Connect the UPS USB cable to your PC or NAS (via Windows/macOS power settings, NUT, or apcupsd) and trigger a clean shutdown once 30โ40% battery remains or after 3โ5 minutes on battery.